Part B fire door regulations in Ireland explained
Under Irish Building Regulations Part B Volume 2, houses with a habitable floor above 4.5 m (3-storey homes and habitable attic conversions) require a protected stairwell enclosed by FD30 (30-minute, 44 mm) fire doors with intumescent strips, cold smoke seals, 3 CE Grade 13 hinges and an EN 1154 overhead self-closer.
When a house or rental legally needs FD30 fire doors, exact gap and hardware tolerances, and what an Assigned Certifier checks.
Free, no obligation. One local fitter prices it, not five.
- > 4.5 mhabitable floor height triggering Part B
- 30 min (FD30)required stairwell enclosure rating
- 2 to 4 mmmax head and jamb gap tolerance
- 3 × Grade 13CE fire hinges required per leaf

Four Irish situations that trigger Part B FD30 fire doors
Attic conversion (habitable 3rd floor)
- Doors needing FD30S upgrade
- New attic room + habitable rooms off landing & hall
- Key statutory detail
- Triggered when top floor sits > 4.5 m above ground
New or existing 3-storey dwelling
- Doors needing FD30S upgrade
- Protected stairwell enclosure on all three levels
- Key statutory detail
- Allows safe escape down stairs without smoke cut-off
Apartment entrance off corridor
- Doors needing FD30S upgrade
- Main flat front door into communal hall
- Key statutory detail
- FD30S with intumescent/smoke seals & working closer
Integral garage door into house
- Doors needing FD30S upgrade
- Pedestrian door between garage and hall/utility
- Key statutory detail
- FD30S self-closing leaf plus 100 mm step or away-slope
Price my doors
Four quick taps and our price shows before we ask for a phone number. One local door fitter rings you, not five.
5 to 8 doors (FD30 fire doors), with new frames, architraves or cassette: €2,500 to €6,200.
How these door installation figures are built
Every range reflects going Irish carpentry and door-fitting rates for that job type, door count and scope. Hang-only figures cover trimming leaves, cutting hinge and latch mortices and fitting customer-supplied ironmongery, with a single-door minimum call-out. Supply-and-hang figures add standard Irish leaves (primed, oak shaker, FD30 fire, glazed or external composite/uPVC) and hardware. New linings, architraves, pocket stud framing or masonry lintels are reflected in the new-frames option and confirmed after an in-person measure. Ask whether VAT is charged at 13.5% or 23% under Revenue's two-thirds rule.
Every component inside a compliant FD30S fire doorset
- 44 mm tested fire leaf (BS 476-22 or IS EN 1634-1). Solid engineered fire core carrying an intact top-edge manufacturer certification label or coloured plug.
- Combined intumescent & cold smoke seal (15×4 mm). Recessed centrally into the lining (or door edge) along the head and both jambs. Expands in heat to seal the frame; brush fin blocks cold smoke immediately.
- Three CE-marked Grade 13 hinges (EN 1935) with intumescent pads. Standard zinc hinges melt in a house fire. Every hinge blade requires a 1 mm mono-ammonium phosphate or graphite pad behind it.
- Overhead self-closing device certified to EN 1154. Must shut the heavy 44 mm leaf squarely into the latch from any angle. Latches and locks also carry CE fire certification with intumescent wrap.
- Fire-rated lining, foam and intumescent acrylic mastics. Gaps between the timber frame and masonry/stud wall must be packed with rockwool or certified fire-rated intumescent foam and sealed under the architraves.
- Perimeter gaps held at 2 to 4 mm (nominal 3 mm). Bottom threshold gap capped at 3 mm where cold smoke control is needed (or fitted with an automatic drop-down smoke seal over flooring).
Why your engineer or Assigned Certifier should review your door schedule first
Attic conversions and open-plan ground-floor layouts vary hugely across Irish estates. Where a ground-floor hallway has been knocked open into a sitting room or kitchen, Part B Volume 2 may require creating a small ground-floor fire lobby, adding an alternative escape route or fitting a residential sprinkler system rather than doors alone. Always confirm the exact room-by-room fire door schedule with your architect or Assigned Certifier before buying leaves. See FD30 fire door installation costs.
Related door fitting guides
FD30 fire doors30-minute fire doors for 3-storey homes, attic conversions and rentals.
Frames, architraves & saddlesWhen old linings can be reused versus fitting new frames and oak saddles.
Hinges, latches & hardwareBall-bearing hinges, mortice latches, thumbturns and external locks.
Irish door sizes & trimming78×30, 80×32 and metric 2040×826 sizing plus safe edge-planing limits.
Door installation DublinPeriod 78×30 frames, attic FD30 retrofits and suburban semi oak sets.
Door installation costFull Irish rate card for hang-only labour, supply-and-fit, frames and VAT.Straight answers before you order doors
Do bathrooms and small cupboards on a 3-storey landing need FD30 fire doors?
Under Part B Volume 2, habitable rooms (bedrooms, sitting rooms, kitchens, offices) opening onto a protected stairwell require FD30 fire doors. Bathrooms and small WCs with no cooking/ignition appliances are generally exempt, though your certifier confirms each doorway on your specific plan.
Can I paint over intumescent strips on a fire door?
Never paint over intumescent strips or smoke brushes. Paint clogs the brush fin and interferes with the strip's chemical expansion in a fire. Mask strips cleanly before decorating frames.
Can I disconnect the overhead door closer once my attic is signed off?
No. Propping open or unhooking an EN 1154 closer defeats the entire stairwell protection if a downstairs kitchen or living room fire starts at night. If you want a living room door held open during the day, fit an acoustic or alarm-linked electromagnetic hold-open closer that releases automatically when the smoke alarm sounds.
How much does an FD30 fire door cost installed in Ireland?
Retrofitting an FD30 leaf into a compliant frame runs €320 to €540. A full pre-hung FD30 doorset with fire-rated lining, seals, closer and architraves runs €480 to €820.